2011 · 13 citations · 6 references
EngineeringElectrical EngineeringEnergy SystemsRenewable Energy IntegrationRenewable Energy SystemsDistributed Energy ResourcesElectricity Load ManagementPower Grid AnalysisPower ManagementRenewable Energy Power ConversionVoltage RegulationGrid Integration Of RenewablesInstalled Capacity AnalysisModal ControlPower FactorReactive Power CompensationReactive Power ControlSolar Photovoltaic InstallationVoltage
We assess the effects that size and locations of photovoltaic (PV) arrays in a low-voltage (LV) electric power grid have on the maximum installable capacity. The objective is to place and control PVs without violating voltage limits and not require interventions by utilities. Multi-modal control is suggested whereby the PVs deviate from unity power factor and begin to supply reactive power if the voltage limits are approached; the installed capacity need not ever be disconnected. Given such multi-modal control, it is shown that the best location of a large PV farm is at the load located furthest away from the medium voltage step-down transformer. Furthermore, we show that the maximum installable capacity increases if the capacity is distributed as many smaller "rooftop" PVs.
6
Josep M. Guerrero, J. Matas, Luis García de Vicuña et al. · IEEE Transactions on Industrial Electronics · 2007 · 1.1K citations
Engineering, Electrical Engineering, Distributed Systems +16
Local Control of Reactive Power by Distributed Photovoltaic Generators
Konstantin Turitsyn, Petr Šulc, Scott Backhaus et al. · 2010 · 199 citations · Full text