Enhanced heat transfer/Journal of enhanced heat transfer · 2001 · 22 citations · 0 references
EngineeringMaterials EngineeringMechanical EngineeringAir ConditioningHeat TransferHvac SystemsAir Conditioning EquipmentAir Conditioning SystemsBuilding Cooling SystemsDuct DesignHvac System DesignThermal DesignAir Conditioning PerformanceCondenser PerformanceCondenser Performance AnalysisCondensersFin DesignFinsHeat Exchanger PerformancePressure Drop
This paper provides an evaluation of the potential for use of brazed aluminum condensers in residential air-conditioning systems. Analysis was done to compare the performance of a brazed aluminum condenser with a presently used 2-row finned tube condenser having 7.0 mm diameter tubes. The comparisons were made for 1-row brazed aluminum designs using 3 × 16 mm or 2 × 20 mm cross-section tubes, whose condensing performance has been measured. Used with a commercially available fin geometry at 26 fins/in, the 3 × 16mm tube design will provide 35% material weight reduction and 15% lower pressure drop, relative to the 7.0 mm round-tube heat exchanger. No cost reduction is predicted. The predicted air-side performance was verified in wind tunnel tests. An advanced fin design having a smaller louver pitch will use 22 fins/in, and provide a 55% material cost reduction. The advanced fin geometry has 8.1 mm high fins, 12 louvers and 1.0mm louver pitch. If a tube having 2.0 mm minor diameter is used, greater air pressure drop reduction will be achieved, but at the expense of material savings.