Resuspension of Dust Particles in a Chamber and Associated Environmental Factors

Jing Qian, Andrea R. Ferro

Aerosol Science and Technology · 2008 · 206 citations · 18 references

DOIFull text

Open access

Concepts

TL;DR

The study used a full‑scale chamber to test particle resuspension from three flooring types (vinyl tiles, new and old level‑loop carpets) under two ventilation configurations, seeding floors with 0.1–10 µm particles and measuring airborne concentrations with optical particle counters. Resuspension rates ranged from 10⁻⁵ to 10⁻² hr⁻¹, increasing with particle size; heavy, fast walking produced higher rates than light walking, likely due to increased pace, air swirl, and electrostatic effects, and new level‑loop carpet yielded significantly higher resuspension than vinyl tile for 1–10 µm particles under a ceiling supply system.

Abstract

Experiments investigating particle resuspension from human activities were conducted in a full-scale experimental chamber. The experiments tested three types of flooring (vinyl tiles, new and old level-loop carpets) and two ventilation configurations (ceiling and side wall supply systems). The floorings were seeded with 0.1–10 μ m test particles. The airborne particle concentration was measured by an array of optical particle counters (OPCs) in the chamber. Resuspension rates were estimated in size ranges of 0.8–1, 1.0–2.0, 2.0–5.0, and 5.0–10 μm ranging from 10−5–10−2 hr−1, with higher resuspension rates associated with larger particles. Resuspension via walking activity varied from experiment to experiment. "Heavy and fast" walking was associated with higher resuspension rates than less active walking, most likely due to a combination of increased pace, increased air swirl velocity, and electrostatic field effects established by the walking. The type of floorings also influenced the particle resuspension. Given the same size and mass distribution of test particles per unit floor area, resuspension rates for the seeded new level-loop carpet were significantly higher than those for the vinyl tile flooring for larger particles (1.0–10 μ m) under the ceiling air supply system.

References

18