Forced Commutation Performance of Vacuum Switches for HVDC Breaker Application

William Premerlani

IEEE Power Engineering Review · 1982 · 16 citations · 0 references

Concepts

Abstract

Tests were conducted to determine performance limits for vacuum switches under forced commutation conditions associated with a highvoltage dc (HVDC) breaker. Circuit parameters were varied and both linear and saturable reactors were used. Single as well as two series breaks were tested. Both ac- and dc recovery voltages were applied. Results confirm that the critical parameters are the current to be interrupted and the time to drive the switch current to zero. A linear reactor works nearly as well as a saturable reactor. Also, the magnitude of current injection need not be matched to the fault current; excess charges preferred.