IEEE Transactions on Power Apparatus and Systems · 1982 · 19 citations · 2 references
Natural SciencesElectrical EngineeringAtmospheric ElectricityCircuit TheoryPower ElectronicsElectrical Hazard AssessmentLightning CurrentLightning ProtectionPower QualityThunderstorm ElectricityThunderstorm ElectrificationCore Loss AnalysisLightning Current In Power SystemsLightning Protection For Power SystemsLightning Protection Of Critical InfrastructureLightning Surge ProtectionSurge Protective DevicesTransformer DesignTransformer Protection
The susceptibility of common designs of single-phase overhead distribution transformers to failure caused by lightning current surges entering the transformer via the normally unprotected low-voltage terminals has been investigated. Evidence from examination of transformers that have failed in service, transient analysis measurements of scaled surges applied to the high-and low-voltage windings, and a full-scale current surge impulse test, indicate that the shell-type designs ut'ilizing a non-interlaced 120/ 240-volt rating are most susceptible to failure. Shell-type and core-type designs with interlaced low-voltage windings are least susceptible. Susceptibility is inversely related to kVA rating, or more specifically, to the volts per turn employed by the designer. With the increasing trend to lower core loss transformers, reducing the volts per turn will increase this hazard on noninterlaced windings.
2