Proceedings of the IEE Part A Power Engineering · 1957 · 14 citations · 0 references
EngineeringElectrical EngineeringInstrumentationMeasurement InvariancePower ElectronicsAngle MeasurementCalibrationElectrical MeasurementEquipment CalibrationAbsolute CalibrationCurrent InjectionElectrical Instrument CalibrationPhase AnglePhase BalanceTest Equipment CalibrationVoltageVoltage Measurement
An account is given of equipment and measuring techniques in use at the National Standards Laboratory, Australia, for calibrating voltage transformers. The equipment employs 3-terminal air-dielectric capacitors to form a voltage divider, the ratio and phase defect angle of which are determined by a self-contained build-up technique. Owing to the use of virtually loss-free capacitors, the phase angle of the divider is negligibly small.Two methods are described for calibrating transformers. In one, ratio balance is obtained by means of a small auxiliary variable-ratio voltage transformer, and phase balance by current injection into one of the detector bridge junctions. In the other method, ratio balance is provided by a variable 3-terminal air-capacitor in the low-voltage arm of the divider, and phase balance by voltage injection in series with that arm, a feedback amplifier providing a low-impedance injection circuit. In both methods the accuracy of measurement is approximately 2 parts in 105 in ratio and 0.05′ in phase angle.The air-dielectric capacitors used in the voltage divider are tested to ensure that they have no significant voltage coefficient of capacitance or loss angle.