Experimental performance of the water/calcium chloride system in a heat transformer

Rosa Marı́a Barragán, Christopher Heard, Víctor Manuel Arellano, R. Best, F.A. Holland

International Journal of Energy Research · 1996 · 31 citations · 6 references

Concepts

Abstract

Absorption heat transformers are devices with the unique capability of raising the temperature of part of a low grade heat source whilst simultaneously delivering the rest of the heat at a lower temperature. The gross temperature lift attainable in the process depends on the characteristics of the working pair. Many combinations of working fluid/absorbent have been proposed although until now the water/lithium bromide system is the most widely used. Experimental results for the water/calcium chloride working pair in an absorption heat transformer are discussed. The highest gross temperature lift was found to be 19°C for an absorber temperature of 84°C. The highest value for the coefficient of performance was found to be 0·45, this means that 45% of the waste heat could be recovered at a higher temperature.

References

6