ERCOT experience with Sub-synchronous Control Interaction and proposed remediation

John Adams, Cathey Carter, Shun-Hsien Huang

2012 · 281 citations · 1 references

Concepts

TL;DR

ERCOT has experienced sub‑synchronous control interaction between Type 3 wind turbines and series‑compensated transmission lines, a problem caused by the interaction of turbine power electronics with these lines, and the region is expanding transmission to support wind generation in CREZ where many lines are series‑compensated. This paper describes the 2009 SSCI event and outlines a plan to protect the grid from future sub‑synchronous control interaction events. The proposed plan implements grid‑protection measures that allow continued wind generation in CREZ while preventing further SSCI events.

Abstract

The Electric Reliability Council of Texas (ERCOT) has experienced sub-synchronous control interaction between Type 3 (Doubly Fed Asynchronous Generator) wind turbines and series compensated transmission lines. The event was due to an interaction between the power electronics of the Doubly Fed Asynchronous Generator and a series compensated transmission line. This paper briefly describes the Sub-synchronous Control Interaction (SSCI) event which occurred in the ERCOT region in 2009. The ERCOT region is in the process of building a major transmission expansion to support transporting wind generated energy from remote regions of the state to populated regions referred to as CREZ. Many of these CREZ lines are series compensated. The paper details a plan to protect the grid against additional sub-synchronous control interaction events while accommodating large amounts of wind generation expected to be installed in the Competitive Renewable Energy Zones (CREZ) grid.

References

1