Electric Power Components and Systems · 2010 · 23 citations · 15 references
Abstract This article presents a simple method for investigating the problem of contemporaneously choosing optimal location and size of shunt capacitors in three-phase unbalanced radial distribution systems. The main objective function formulated consists of two terms: cost of energy loss and cost related to capacitor purchase and capacitor installation. The problem of choosing optimal locations and sizes for shunt capacitors in an unbalanced radial distribution system is addressed with the two algorithms in this article—one is for selecting the best locations of capacitor placement and candidate node identification algorithm; the second is for the sizing of capacitors, a variational technique algorithm according to available standard size of capacitors. The objective function used in this article is to maximize the net savings in the distribution system. This article presents the results of simulations for 25-bus and IEEE 37-bus unbalanced radial distribution systems.
15
Radial distribution test feeders
W.H. Kersting · IEEE Transactions on Power Systems · 1991 · 1.9K citations
Industrial Distribution, Engineering, Power Grid Operation +14
Distribution system power flow analysis-a rigid approach
T.-H. Chen, M.-S. Chen, Kab Ju Hwang et al. · IEEE Transactions on Power Delivery · 1991 · 499 citations