Journal of Building Performance Simulation · 2014 · 35 citations · 2 references
ArchitectureArchitectural EngineeringBuilding ScienceAir ConditioningHvac SystemsVentilationAir Conditioning SystemsBuilding AutomationBuilding Automation SystemsBuilding Energy ModelingBuilding Energy SystemsHvac System SimulationAir Conditioning ModelingBuilding Energy Performance SimulationEnergy ConsumptionEnergy PerformanceEnergy Savings AssessmentEnergyplus ModelingHvac Energy UseSupply Air Temperature Reset
Today, many large commercial buildings use building automation systems to manage a wide range of equipment. This paper investigates the energy savings potential of several common heating, ventilation, and air conditioning (HVAC) system re-tuning measures on a typical large office building using the EnergyPlus software. Individual re-tuning measures simulated include automatic schedule adjustments, damper minimum flow adjustments, thermostat adjustments, as well as dynamic resets to static pressure, supply-air temperature, condenser chilled- and hot-water temperatures, and chilled and hot water differential pressure set points. All individual measures and combinations were simulated in 16 locations representative of different climates in the USA. Many of the demand-side individual measures were capable of reducing annual HVAC energy consumption by over 20% in most cities. Supply-side measures affecting HVAC plant conditions were only modestly successful (less than 5% annual HVAC energy savings). Some of the combinations revealed between 35% and 75% HVAC energy savings.
2
Irwin Weintraub · Electronic Green Journal · 2000 · 89 citations · Full text
Engineering, Architectural Engineering, Building Science +11