IEEE Transactions on Power Systems · 1992 · 186 citations · 3 references
EngineeringElectrical EngineeringSystems EngineeringAir ConditioningCircuit TheoryPower ElectronicsElectrical System DiagnosticsPower QualityPower System ReliabilityPower System StabilityPower SystemsVoltage RegulationCompressor SystemsOvervoltage TransientsPower System Fault AnalysisPower System Fault TransientsTransmission System ReliabilityVoltage Interruption
Southern California Edison Company (SCE) has experienced delayed voltage recovery following fault clearing on the transmission system. The authors describe these occurrences and document the studies which successfully modeled the voltage recovery process. The studies showed how the stalling of single-phase air conditioner compressors following a power system fault was the root cause of delayed voltage recovery. Tests of air conditioner response to voltage dips are documented. The results of these tests are used to derive the mathematical load models used in voltage recovery studies.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>