IEEE Transactions on Power Apparatus and Systems · 1983 · 28 citations · 7 references
Transmission LinesElectrical EngineeringEngineeringSensorsMeasurementElectrical TransmissionComputer EngineeringGround LevelHigh Voltage DcEducationElectric Power TransmissionTransmission LineComputational ElectromagneticsVertical Current DensityInstrumentationElectrical InsulationElectromagnetic Compatibility
Sensors for measuring vertical current density at ground level near high voltage dc (HVDC) transmission lines are subject to error when the sensor is not in the ground plane. The magnitude of this error, for guarded and unguarded sensors, has been investigated using hoth dc electric fields with space charge and ac electric fields in a parallel plate facility. For conditions like those expected under HVDC transmission lines, the results obtained using ac and dc methods agreed to within experimental uncertainty. The measuired errors are as large as 25 percent for guarded sensors and significantly larger for unguarded sensors. Data for various sensor elevations and guarding are presented in graphs to aid the designer. Comparisons with results from an IEEE Working Group field day are also presented.
7