IEEE Transactions on Industry Applications · 2014 · 22 citations · 2 references
EngineeringElectrical EngineeringSystems EngineeringPower ElectronicsRadiation ProtectionRenewable Energy IntegrationElectrical Hazard AssessmentPhotovoltaic DevicesPower Electronics For Renewable EnergyPower System DesignRenewable Energy Power ConversionSolar Photovoltaic SystemsArc Flash Hazard AssessmentArc Flash PreventionElectrical System AssessmentElectrical System IntegrationFlash CalculationsFlash ExposureShort-circuit CurrentShort-circuit Protection
When planning for the installation of a 1.3-MW photovoltaic (PV) system and its integration into an existing facility's electrical system, an arc flash study was performed to determine the best protective device settings to minimize the arc flash energy in the PV system and to determine the effect of the additional short-circuit current on arc flash calculations for the existing system. The existing system has distribution at 13.8 kV and two 10-MVA transformers to a 2.4-kV feeder system. The PV system adds the hazard of 500-Vdc subarray collection wiring and terminations. The dc arc flash exposure of PV systems, including those in the inverter enclosures, can be complicated, and this paper outlines the basic data collected for the study, the steps taken to complete the calculations, the methodology used, the results, and the team's learnings.
2