IEEE Transactions on Power Apparatus and Systems · 1964 · 22 citations · 3 references
EngineeringElectrical EngineeringPhysicsCircuit TheoryElectromagneticsElectromagnetismElectrical ConductivityMagnetic Circuit AnalysisOhm's LawRelative PermeabilityTransmission LinesCable Electromagnetic FieldsCable SystemsCharacteristic ImpedanceElectrical ImpedanceImpedance AnalysisMagnetic PropertiesPhase Sequence
The positive or negative phase sequence impedance of a pipe-type cable may be calculated by conventional formulas, suitably modified to include the effect of magnetic properties of the pipe. Calculation of the zero phase sequence impedance, however, is considerably more complicated, involving not only the permeability of the steel pipe, which depends upon the zero phase sequence current, but also the resistance of the shield skid wire assemblies. Formulas and curves are presented by which the zero phase sequence impedance may be determined for any particular case.
3