Concepedia

Publication | Closed Access

Integrated Modeling and Enhanced Control of DFIG Under Unbalanced and Distorted Grid Voltage Conditions

106

Citations

20

References

2012

Year

Abstract

This paper focuses on the enhanced control and improved fault-ride-through capability of a doubly fed induction generator (DFIG)-based wind turbine system under both unbalanced and distorted grid voltage conditions. A more integrated mathematical model of DFIG is first set up with both the negative-sequence and the low-order harmonic grid voltages considered. Based on the developed model, the instantaneous active/reactive powers and electromagnetic toque are redefined in detail. Besides, four alternative control targets and their corresponding rotor current references are calculated and assigned. A novel current controller, consisting of a conventional PI regulator and a dual-frequency resonant (DFR) compensator, tuned at twice and six times the grid frequency, named PI-DFR controller, is designed to regulate the fundamental and the fifth- and seventh-order harmonic components simultaneously. Experiment studies verify the correctness of the developed model and the effectiveness of the suggested control strategies in improving the fault-ride-through capability of a DFIG system under such adverse grid conditions.

References

YearCitations

Page 1