Publication | Closed Access
An improved method for the digital protection of high voltage transmission lines
73
Citations
7
References
1975
Year
Electrical EngineeringDigital ProtectionImproved MethodFault OccurrenceEngineeringLong LineElectrical TransmissionComputer EngineeringTransmission LineElectric Power TransmissionDigital MethodsTransmission SystemPower System ProtectionPower System TransientPower Electronic DevicesElectromagnetic Compatibility
This paper explores the accuracy of the digital methods for protection of high voltage transmission lines under transient fault condition on a long line and describes an improved method for future digital protection schemes. With this method it is possible to calculate R and L of high voltage transmission lines so that any number of harmonics on the current and voltage waveforms can be eliminated and it is shown to be suitable for distance protection during the first cycle of fault occurrence.
| Year | Citations | |
|---|---|---|
Page 1
Page 1