IEEE Transactions on Power Delivery · 1996 · 33 citations · 3 references
EngineeringCivil EngineeringElectrical EngineeringCircuit TheoryCorrosion SciencePower ElectronicsElectrical CharacterizationElectrical ConductivityElectrical InstallationInsulation MaterialsInsulation SystemsTransmission LinesCable InsulationCable SystemsDegradationElectrical Breakdown StrengthElectrical PropertiesElectrical Properties AnalysisInsulation Degradation AssessmentInsulation Performance
500-kV XLPE-insulated cable with an insulation thickness of 27 mm has been developed for long-distance transmission lines. Basic studies on 500-kV XLPE cable have shown that contaminants in the insulation may be the factor determining electrical performance. This hypothesis is justified by the good correlation obtained between statistical estimations of the size of the largest contaminant in the insulation and the electrical characteristics of full-sized cables. Voltage-withstand and long-term tests have confirmed the design values for minimum breakdown stress, for AC and impulse voltage, and for the degradation coefficients.