Review of Scientific Instruments · 1949 · 13 citations · 5 references
EngineeringElectrical EngineeringEquipmentInstrumentationPower ElectronicsElectric PotentialElectrical MeasurementInstrumentation AmplifiersVoltage RegulationVoltage RegulatorsHigh-voltage MeasurementHigh-voltage Power SupplyHigh-voltage Power SystemsImpedance MeasurementVoltageVoltage MeasurementVoltage StabilityVoltage-controlled Instruments
An a.c. operated power supply has been developed which furnishes voltage for the electrostatic analyzers for the University of Wisconsin electrostatic generator. Voltage is continuously variable from about 5000 to 50,000 with stability and accuracy of measurement within ±0.01 percent. The stabilizer is of the usual degenerative type, but the error signal is amplified by a phototube galvanometer d.c. amplifier and applied to a series impedance in the high voltage transformer primary circuit. The generator beam energy automatically follows adjustments of a low voltage potentiometer used for voltage measurements in this supply.
5
Absolute Voltage Determination of Three Nuclear Reactions
R. G. Herb, S. Snowdon, O. Sala · Physical Review · 1949 · 132 citations
R. M. Ashby, A. O. Hanson · Review of Scientific Instruments · 1942 · 16 citations