Leak detection in pipes by frequency response method using a step excitation

Witness Mpesha, M. Hanif Chaudhry, Sarah L. Gassman

Journal of Hydraulic Research · 2002 · 113 citations · 10 references

Concepts

TL;DR

Leakage in piping systems produces secondary resonant pressure peaks in the frequency response diagram that are lower than the primary peaks observed in leak‑free systems. The study proposes a new procedure that uses transient state pressures to detect leaks in piping systems. The method analyzes transient flow generated by valve actuation with the method of characteristics, transforms the time‑domain data to the frequency domain via FFT to create a frequency response diagram, and determines leak location from the primary and secondary pressure peaks and discharge from amplitude extremes, applicable over a friction factor range of 0.01–0.025 and requiring only a single downstream measurement location.

Abstract

This paper presents a new procedure utilizing transient state pressures to detect leakage in piping systems. Transient flow, produced by opening or closing a valve, is analyzed in the time domain by the method of characteristics and the results are transformed into the frequency domain by the fast Fourier transform. This method is used to develop a frequency response diagram at the valve end. The frequency response diagram of a system with leaks has additional resonant pressure amplitude peaks (herein called the secondary pressure amplitude peaks) that are lower than the resonant pressure amplitude peaks for the system if there were no leaks (herein called primary amplitude peaks). The location of a leak is determined from frequencies of the primary and secondary pressure amplitude peaks and the leak discharge is determined from the maximum and minimum discharge amplitudes. This method is applicable for practical values of the friction factor over the range 0.01 to 0.025 and can be used to detect leaks in real-life pipe systems conveying different types of fluids, such as water and petroleum. It can be used directly by comparing the frequency response diagram of a modeled system without leaks to the frequency response diagram developed by gradually opening or closing a valve at the downstream end of a pipe and taking measurements of pressure head and discharge at only one location.

References

10