EngineeringEmergency PlanningMechanical EngineeringComputational Fluid DynamicsComputational Heat TransferFire ManagementAirflow SimulationFire ModelingFire SimulationFire TestingSmoke SimulationVentilation ModelingCfd SimulationComputational Fluid Dynamics Fire SimulationHeat Release RateHeat Release Rate ModellingSmoke ProductionTunnel Fire ModelingTunnel Fire SimulationYield Per Unit Area
The present study clarified the smoke generation rate in a tunnel fire, which is essential data for the planning of emergency measures. The smoke generation rate was determined by the least squares method using the results of full-scale tunnel fire experiments and three-dimensional CFD simulation. The following results were obtained. The smoke generation rate per unit area increases gradually with pool fire area, 3.12 to 4.35 g/(s•m2) in the case of 1 m2, 4.18 to 5.85 g/(s•m2) in the case of 4 m2. When pool fire area becomes 9 m2, the smoke generation rate per unit area increases rapidly to 10.1 g/(s•m2). The smoke yield by gasoline reducing rate in the case of a gasoline pan fire with an area of 4 m2 is approximately 4.4 - 6.8 % and reaches around 11 % when the area increases to 9 m2. The heat release rate and smoke generation rate in the case of a large bus fire is nearly equal to a gasoline pan fire of 9 m2.