Geothermal Energy · 2015 · 151 citations · 20 references
EngineeringArchitectural EngineeringMechanical EngineeringComputational Heat TransferHeat TransferThermal AnalysisHeat ExchangersHeat FlowHeat Transfer AnalysisHeat Transfer In BuildingsHeat Transfer ModelingThermal DesignConvective Heat TransferEarth Air Heat ExchangersFriction FactorHeat Exchanger DesignNumerical Thermal ModelsNusselt NumberPressure DropThermal Performance Modeling
The earth–air heat exchanger (EAHE) is a promising technique which can effectively be used to reduce the heating/cooling load of a building by preheating the air in winter and vice versa in summer. In the last two decades, a lot of research has been done to develop analytical and numerical models for the analysis of EAHE systems. Many researchers have developed sophisticated equations and procedures but they cannot be easily recast into design equations and must be used by trial-and-error. In this paper, the author has developed a one-dimensional model of the EAHE systems using a set of simplified design equations. The method to calculate the earth’s undisturbed temperature (EUT) and more recently developed correlations for friction factor and Nusselt number are used to ensure higher accuracy in the calculation of heat transfer. The developed equations enable designers to calculate heat transfer, convective heat transfer coefficient, pressure drop, and length of pipe of the EAHE system. A longer pipe of smaller diameter buried at a greater depth and having lower air flow velocity results in increase in performance of the EAHE system.
20