2005 · 32 citations · 4 references
EngineeringElectrical EngineeringCircuit TheoryFault TolerancePower ElectronicsFault ModelingPower Grid AnalysisThree-phase CircuitsBalanced Three-phase SystemsCircuit Fault AnalysisCurrentsFault AnalysisShort-circuit AnalysisSymmetrical ComponentsUnbalanced Three-phase Systems
The computation of short circuit currents for unbalanced faults in a normally balanced three-phase system has traditionally been accomplished by the application of the method of symmetrical components. However, this method is not as well suited to a distribution feeder that is inherently unbalanced. For example, it is important to be able to compute line-to-ground faults that occur on phases b and c and line-to-line faults that occur on phases other than just b and c. This paper will develop a method for computing all combinations of fault currents using the phase frame of reference. A sample system will be used to demonstrate the method.
4
Radial distribution test feeders
W.H. Kersting · IEEE Transactions on Power Systems · 1991 · 1.9K citations