A combined method to efficiently adjust frequency-based anti-islanding relays of synchronous distributed generation
15
Citations
13
References
2014
Year
Electrical EngineeringEngineeringPower Grid OperationSmart GridFrequency RelaysFrequency-based RelaysFrequency-based Anti-islanding RelaysPower System ControlGrid StabilityPower System ProtectionFrequency ControlPower Imbalance ArCombined MethodPower System Analysis
An important requirement for interconnecting distributed generation is anti-islanding protection. This paper uses the capabilities of two methods, application region (AR) and power imbalance AR, to efficiently adjust frequency-based relays. The proposed method gives a proper simple and nonexpensive solution to the synchronous distributed generation islanding detection problem. It employs the common protection devices: frequency or rate of change of frequency relays. These relays are adjusted in order to satisfy the anti-islanding protection and safe and abnormal frequency variation requirements and also to discriminate between islanding and nonislanding disturbances. The procedure is applied to a real system, which is a portion of the Isfahan Regional Electric Network in Iran, to show the effectiveness of the proposed approach. Copyright © 2014 John Wiley & Sons, Ltd.