2002 · 30 citations · 0 references
EngineeringElectrical EngineeringCircuit TheoryInterconnection NetworksSystem DynamicsDistributed Energy ResourcesDistribution NetworksEnergy System ModelingPower Grid AnalysisPower SystemsSimulation MethodsDistribution Network ModelingElectric Power System ModelingGeneratorsLoad Flow AnalysisMagnetizing CurrentPower Distribution NetworksPower System Modelling
Operation problems that result from MV distribution networks with local asynchronous generation sources connected are examined. In order to analyze steady-state operating situations, a load-flow calculation must be performed. The presence of asynchronous generators imposes the adoption of a consistent bus modelization using a new bus type, the PX bus, where P is the active generated power and X is a nonlinear magnetizing reactance. This approach introduces some modifications in the conventional load-flow algorithms, thereby increasing the total number of iterations.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>