AIP conference proceedings · 2002 · 21 citations · 0 references
EngineeringChemical EngineeringMechanical EngineeringAir ConditioningHeat TransferThermal AnalysisCooling SystemsRefrigerationRefrigeration CyclesRefrigeration SystemsCarnot EfficiencyCompressor SystemsIndustrial RefrigerationMulti-stage Refrigeration SystemsRefrigerantsRefrigeration Cycle AnalysisRefrigeration Performance AnalysisThermodynamic Analysis
The efficiency of coolers designed to provide refrigeration for industrial equipment is discussed. Experience accumulated during more than twenty years of manufacturing shows that multistage auto-cascade coolers provide high refrigeration performance along with rapid cool down and defrost. Both single-stage and two-stage throttle cycles have been analyzed. Comparative data on the performance of the cycles are obtained with a computer model that includes an equation of state to calculate thermodynamic properties of mixed refrigerants. Both flammable argon-hydrocarbon- and nonflammable argon-hydrofluorocarbon-based mixed refrigerants have been considered. Non-flammable environmentally friendly mixed refrigerants include commercially available components. The experimental data were obtained for coolers based on a single-stage compressor. The tested systems provided refrigeration capacity from 500 to 3600 W depending on the compressor displacement volume. A Carnot efficiency coefficient as high as 0.21 was achieved. This corresponds to the efficiency of conventional freezers operating at temperatures above 230 K.