Mitigation method of 3rd-harmonic voltage for a three-phase four-wire distribution system based on a series active filter for the neutral conductor

Keiji Wãda, Toshihisa Shimizu

Conference Record of the 2002 IEEE Industry Applications Conference. 37th IAS Annual Meeting (Cat. No.02CH37344) · 2003 · 28 citations · 9 references

Concepts

Abstract

This paper proposes a series active filter for mitigation of the 3rd-harmonic voltage in a three-phase four-wire power distribution system in a building. The active filter which consists of a single-phase inverter can suppress the harmonic voltage of the system. The active filter is characterized by acting not only as a capacitor but also as a resistor for the 3rd-harmonic components. A Hilbert transformer is applied to the controller of the active filter in order to realize the accurate 3rd-harmonic detection on a single-phase active filter. Measurement results of harmonic distortion of source voltage in a building are also shown in this paper. It is clarified in a simulation and experiment that the active filter can suppress the 3rd-harmonic voltage without increasing neutral conductor current.