Improving DOE-2's RESYS routine: User defined functions to provide more accurate part load energy use and humidity predictions

Hugh Henderson, Danny Parker, Yu Huang

University of North Texas Digital Library (University of North Texas) · 2000 · 34 citations · 2 references

Full text

Open access

Concepts

Abstract

In hourly energy simulations, it is important to properly predict the performance of air conditioning systems over a range of full and part load operating conditions. An important component of these calculations is to properly consider the performance of the cycling air conditioner and how it interacts with the building. This paper presents improved approaches to properly account for the part load performance of residential and light commercial air conditioning systems in DOE-2. First, more accurate correlations are given to predict the degradation of system efficiency at part load conditions. In addition, a user-defined function for RESYS is developed that provides improved predictions of air conditioner sensible and latent capacity at part load conditions. The user function also provides more accurate predictions of space humidity by adding ''lumped'' moisture capacitance into the calculations. The improved cooling coil model and the addition of moisture capacitance predicts humidity swings that are more representative of the performance observed in real buildings.

References

2