2005 · 79 citations · 4 references
EngineeringElectrical EngineeringPhysicsCorrosion ScienceElectrochemistryFire Protection EngineeringElectrical CharacterizationElectrical Hazard AssessmentElectrical Hazard IdentificationElectrical System DiagnosticsInsulation SystemsCondition Monitoring Of InsulationElectrical InsulationElectrical Insulation MaterialsInsulation Defect DetectionInsulation DiagnosticsInsulation Fault DiagnosisPartial DischargePartial Discharge Testing
Partial discharge (pd)-based risk assessment in electrical insulation systems becomes effective only if the nature of the defect generating pd can be ascertained. In oil/paper insulation systems this is a fundamental item since e.g. harmfulness of pd generated by gas bubbles is much smaller than that of pd occurring between paper layers. For such reasons, partial discharge analysis of oil/paper insulated systems often lacks a clear correlation between cause (i.e., defect type) and effect (partial discharge recording). Results relevant to partial discharge measurements performed on lab-scale objects having different electrode configuration are presented in the paper with the purpose to spotlight characteristic features aimed at identifying the basic nature of partial discharge-generating defects in oil/paper insulated systems.
4
Discharges in combined transformer oil/paper insulation
G. Berg, L.E. Lundgaard · 2003 · 22 citations
Experience on partial discharge monitoring of power transformers
Enrico Vellucci, A. Cavallini, G.C. Montanari et al. · 2005 · 12 citations