A Comparison Of An R22 And An R410A Air Conditioner Operating At High Ambient Temperatures

William V. Payne, Piotr A. Domanski

Purdue e-Pubs (Purdue University System) · 2002 · 34 citations · 3 references

Full text

Open access

Concepts

Abstract

R22 and R410A split air-conditioning systems were tested and compared as outdoor temperature ranged from 27.8 C (82.0 F) to 54.4 F (130 F).The R410A system tests were extended to 68.3 C (155.0 F) ambient temperature with a customized compressor.Capacity and efficiency of both systems decreased linearly with increasing outdoor temperature, but the R410A system performance degraded more than the R22 system performance.Operation of the R410A system was stable during all tests, including those with the customized compressor extending up to the 68.3 F (155.0 F) outdoor temperature and resulting in a supercritical condition at the condenser inlet.No noticeable changes in noise level or operation of the system was noted. NOMENCLATUREComp compressor COP coefficient of performance, W/W EER energy efficiency ratio, Btu/Wh SEER seasonal energy efficiency ratio, Btu/Wh T ambient temperature, C (F)T cond condenser temperature, K scfm standard cubic feet per minute (defined by ASHRAE Standard 37) T evap evaporator temperature, K TXV thermostatic expansion valve