EFFECT OF CHLORIDE AND SULFATE CONTAMINATION IN SOILS ON CORROSION OF STEEL AND CONCRETE

Omar S. Baghabra Al‐Amoudi, Sabel N Abduljauwad, Rasheeduzzafar, Mohammed Maslehuddin

Transportation Research Record Journal of the Transportation Research Board · 1992 · 26 citations · 3 references

Concepts

Abstract

The durability performance of plain and blended cements in sabkha soils (soils contaiminated with high concentrations of chloride and sulfate salts) was investigated. Specimens placed in the sabkha soil were obtained at periodic intervals and evaluated by conducting strength loss measurements, corrosion potentials monitoring, and corrosion rate measurements at regular intervals. Results indicate that the strength reduction after 540 days of exposure to sabkha soils was greater in silica fume cement mortar specimens compared with plain and other blended cements. Reinforcement corrosion was, however, much lower in silica fume cement concrete than in plain, fly ash, and blast furnace slag cements. This indicates that use of silica fume cement in structural components placed in sabkha soils will be beneficial from the viewpoint of reinforcement corrosion. Additional protective measures, such as application of a water-resistant epoxy-based coating, will have to be adopted to minimize deterioration related to sulfate salts.