Purdue e-Pubs (Purdue University System) · 1988 · 10 citations · 0 references
Open access
EngineeringArchitectural EngineeringMechanical EngineeringAir ConditioningEnergy SystemsHeat TransferAir Conditioning EquipmentAir Conditioning SystemsHeat ExchangersHeat PumpsRefrigerationRefrigeration SystemsEvaporator PerformanceHeat Distribution EfficiencyHeat Exchanger EfficiencyHeat Exchanger PerformanceHeat Flux ExchangeHeat Pump SystemsRefrigerant MixturesRefrigerants
An experimental, water-to-water , breadboard heat pump, that is one which could easily be reconfigured, was constructed for comparison of pure R22 to the refrigerant mixtures R22/R114 ahd R13/Rl2.Three evaporator configurations were extensively studied.In all cases the best mixture outperformed R22.The best efficiency with R22/Rl14 was 32% higher and with R13/Rl2 was 16% higher than the best e~ficiency measured with R22.other obseryations were, first, that mixtures can take advantage of heat exch~nger efficiency that, ih a gliding temperature application; a pure refrigerant is incapable of utilizing.Secondly, that heat exchange between the condensed and evaporating refrigerant is beneficial to some mixed refrigerants . .Finally, mixtures exhibit nonlinearity of enthalpy versus temperature in the two phase region which has significant impact on both heat exchanger and cycle design.