Nuclear Engineering and Technology · 1995 · 10 citations · 0 references
EngineeringElectrical EngineeringSystems EngineeringPower ElectronicsElectrical System DiagnosticsMesh AnalysisPower Grid AnalysisPower System DesignPower System StabilityPower SystemsElectric Power System ModelingPower Distribution AnalysisPower Distribution NetworksPower System ModelingPower System Modelling
This paper examines the applicability of the modified Borresen's coarse-mesh method(MBSN) to the core power distribution monitoring program development for the Yonggwang nuclear power plant unit 3(YGN 3) which uses fixed incore detectors for monitoring core power distribution. In so doing the modified Borresen's coarse-mesh equations are solved with core internal boundary conditions provided by the fixed incore detectors and three-dimensional core power distributions are com puted for the first-cycle core of the YGN 3 PWR. The results are compared with predictions of the COLSS(Core Operating Limit Supervisory System) which is the axial power shape monitoring program of the YGN 3. It is shown that the modified Borresen's method can reproduce the core axial power shape more closely than the COLSS. Because of other advantages in computing speed and predictive capability, n conclude that the proposed MBSN has a promising practical application for core power distribution monitoring program development