EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionFault ToleranceProtection SystemsTransmission LinesDirectional ProtectionNegative Sequence CurrentsProtection RelayingProtective RelayingRelay NetworksRelay ProtectionRelays
Directional overcurrent relaying (67) refers to relaying that can use the phase relationship of voltage and current to determine direction to a fault. There are a variety of concepts by which this task is done. This paper reviews the mainstream methods by which 67 type directional decisions are made by protective relays. The paper focuses on how a numeric directional relay uses the phase relationship of sequence components such as positive sequence (V <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">1</sub> vs. I <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">1</sub> ), negative sequence (V <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub> vs. I <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub> ), and zero sequence (V <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">0</sub> vs. I <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">0</sub> ) to sense fault direction, but other concepts such as using quadrature voltage (e.g., V <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">ab</sub> vs I <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">c</sub> ) are included