Empirical Modeling of a Rolling- Piston Compressor Heat Pump for Predictive Control in Low Lift Cooling

Nicholas Gayeski, Tea Žakula, Peter R. Armstrong, Leslie K. Norford

DSpace@MIT (Massachusetts Institute of Technology) · 2010 · 13 citations · 9 references

Full text

Open access

Concepts

Abstract

Measured performance and empirical modeling of an inverter-driven variable capacity heat pump are developed for use in a predictive control algorithm to achieve energy-efficient low-lift heat pump operation.A 0.75 refrigeration ton heat pump with rolling-piston compressor was tested at 131 steady-state operating conditions spanning pressure ratios from 1.2 to 4.8.Compressor speed, condenser fan speed, condenser air inlet temperature and evaporator air inlet temperature were varied to map the performance of the heat pump over a broad range of conditions including very low compressor speeds and pressure ratios.Empirical, regression-based curve-fit models of the heat pump power consumption, cooling capacity, and coefficient of performance were identified that accurately represent heat pump performance over the full range of test conditions.This model can be incorporated into model-based predictive chiller control algorithms where compressor speed, condenser fan speed and evaporator fan (or chilled water pump) speed can be varied in an optimal way to achieve significant annual cooling system energy savings.

References

9