Purdue e-Pubs (Purdue University System) · 2010 · 28 citations · 0 references
Open access
EngineeringMechanical EngineeringAir ConditioningHeat TransferHeatingAir Conditioning EquipmentAir Conditioning SystemsEnergy Efficiency In HeatingHeat PumpsHvac System DesignRefrigeration SystemsAir Conditioning PerformanceCondenser PerformanceHeat Pump SystemsHeat Pump TechnologyVapor Compression CycleVapor Compression Heat Pumps
In the present study we have carried out the drop-in experiments of R410A, HFO-1234ze(E) and the mixture of 50mass%HFO-1234ze(E)/50mass%HFC-32 at heating mode, using a vapor compression heat pump system developed for R410A. It has found that in the case of mixture of 50mass%HFO-1234ze(E)/50mass%HFC-32 the COP value is little affected by the degree of subcooling at the condenser outlet and it is only about 7.5% lower than that of R410A at the same heating load of 2.8 kW. This reveals that mixtures of HFO-1234ze(E)/HFC-32 are considered to be applicable as low-GWP alternatives for R410A by adjusting the composition of the mixture and by reconsidering the design parameters of components of room air-conditioning system.