Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems · 1952 · 11 citations · 3 references
EngineeringElectrical EngineeringAnalog ElectronicsCircuit TheoryPower ElectronicsElectric CircuitsElectrical System DiagnosticsPower QualityPower System ReliabilityPower System StabilityPower SystemsBreakersCircuit Breaker TestingCurrentsFault AnalysisHigh-voltage Power SystemsPower System Fault TransientsPower System ProtectionSwitching Transients
This paper comprises an analytic study of dynamic voltages to be expected at the terminals of a tie-line circuit breaker during the separation of two parts of a system 180 degrees out of phase. Transient voltage crests have been investigated on the analogue computer for a typical system under faulted and unfaulted conditions and the results are compared with oscillographic records obtained on an actual power system. Finally, high power laboratory data obtained on modern high-voltage circuit breakers opening fault currents at twice normal voltage and higher are evaluated in the light of the maximum possible duty indicated by the analytic study.
3