OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1990 · 70 citations · 0 references
EngineeringWater Resources ManagementDesign OptimizationHeat TransferOptimizationAir Conditioning SystemsChilled Water SystemsCooling Load CalculationCooling SystemsCooling Tower SystemsHeat Transfer ModelingChiller Performance ModelingControl Algorithm DevelopmentCooling System ControlsCooling Tower Control SystemsCooling Tower PerformanceCooling Tower Performance ModelingOpen-loop ControlOpen-loop Optimal Control
This paper presents an algorithm for near-optimal control of cooling towers. The algorithm is based upon an open-loop control equation in terms of the total chilled-water cooling load. The parameters of this equation may be estimated from design data with relations derived from a simple model for cooling tower and chiller power trade-offs with tower control. Results of the near-optimal control algorithm are compared with the true optimal solution applied to detailed simulation model. The algorithm is extremely simple and is easily implemented in existing systems.