2002 · 66 citations · 1 references
EngineeringElectrical EngineeringGeophysicsElectromagneticsElectromagnetismGeotechnical EngineeringElectrical CharacterizationElectrical ConductivityElectrical Conductivity Of SoilsElectrical MeasurementOhm's LawElectrical Resistivity Of SoilsElectrode DesignElectrode Impedance CharacterizationField MeasurementsSoil ElectrodesSoil Resistivity
In highly resistive soils, long vertical rods are used to lower ground resistance, yet their inductive behaviour can make high‑frequency impedance exceed low‑frequency resistance. The study demonstrates, via field measurements, that a critical length exists for ground rods or wires. Electrodes shorter than the critical length exhibit capacitive behavior with high‑frequency impedance below resistance, whereas longer electrodes show inductive behavior with impedance rising with frequency, confirmed by simple modeling.
To reach a low ground resistance value in very resistive soil, long vertical rods are often used. But due to the inductive behaviour of long electrodes, high frequency ground impedance could be much greater than its resistance at low frequency. Based on field measurements, this paper shows the existence of a critical length for ground rods or wires. An earth electrode shorter than the critical length has HF impedance lower than its resistance (capacitive behaviour). On the other hand, for greater lengths, the HF impedance increases as a function of the frequency (inductive behaviour). A simple modelling confirms these results.
1
Earth Conduction Effects in Transmission Systems
Students Quarterly Journal · 1949 · 1.3K citations