2000 · 39 citations · 4 references
EngineeringEducational TechnologyAir ConditioningHvac SystemsVentilationAir CirculationAir Conditioning EquipmentAir Conditioning SystemsAir Distribution SystemsAirflow DistributionVentilation SystemsAir DistributionAir Distribution DesignAir Distribution EquipmentAir Distribution System DesignClassroom Ventilation
This study involves comprehensive experimental measurements and CFD simulations in a mock-up of a full-size classroom with realistic loads. Four different air distribution systems have been tested: • Mixing ventilation produced from a high velocity ceiling supply device • Bag-supply (textile) device located in the ceiling • Displacement ventilation using a standard low velocity air supply device • A down-to-floor impinging jet air supply device. The measured wall temperatures have been used as boundary conditions for the CFD simulations. Predicted and measured quantities are: air velocity, air temperature, ventilation effectiveness and local mean age of air. The down-to- floor impinging jet was also tested in a field trial.
4
Building ventilation: theory and measurement
Choice Reviews Online · 1997 · 742 citations
Engineering, Architectural Engineering, Building Science +17
What is ventilation efficiency?
Mats Sandberg · Building and Environment · 1981 · 410 citations
Inefficiency of upward displacement operating theatre ventilation
B. Friberg, Sven Friberg, Lars Burman et al. · Journal of Hospital Infection · 1996 · 47 citations
Engineering, Surgery, Hvac Systems +13